Operating Range
0°C to 65°C
Ambient Temperature
10°C to 40°C non-condensing
Stability / Repeatability
± 0.05°C at constant load (even near ambient)
Cooling Capacity*
265-400 watts @ 20°C (20°C ambient)
depending on model and configuration
Noise (at 1 meter)
< 50 dBA with 50% load, < 63 dBA with full load
Coolant / Process Fluid
Koolance (27% propylene glycol / water mix)
or 27-50% ethylene glycol / water mix
Process Fluid Fittings
1/4" valved CPC or 1/4" swage
Pump
Centrifugal pump or Magnetic Drive Gear Pump
Flow Rate
Centrifugal: >3 lpm @ 10 psig, ~1.5 lpm @15 psig
Gear Pump: 3 lpm @ 30 psig (factory adjustable)
Tank Volume
1 liter with level sensor
Wetted Materials
Aluminum or Stainless Steel cold plate with compatible wetted materials
Size (W x D x H)
19" x 16" x 7" 4U (48 cm x 41 cm x 18 cm)
Power Input
Universal: 100-240 VAC, 50/60 Hz
Controls
Digital PID controller for heating and cooling
Communications
RS232, RS485, or Ethernet
Alarms
Temperature, fluid level, system or component
failure (display and remote)
Standards
RoHS compliant, TUV listed to UL and CE Pending
* Note: Cooling capacity will vary with configuration